Skip to main content

Full text of "BSTJ 48: 10. December 1969: Physical and Transmission Characteristics of Customer Loop Plant. (Gresh, Philip A.)"

See other formats


Physical and Transmission Characteristics 
of Customer Loop Plant 

By PHILIP A. GRESH 

(Manuscript received June 17, 1969) 

This report covers the principal physical and transmission character- 
istics of the Bell System customer loop plant. Items covered include a 
statistical characterization of physical composition, measured and cal- 
culated transmission characteristics, and measured noise and crosstalk 
performance. A survey conducted in 1964 provided the data base for this 
report and comparisons of data obtained from a similar survey in 1960 
illustrate that, in many respects the composition of loop plant changes only 
slowly with time. Consequently, the 1964 survey results are believed to be 
representative of today's plant. 

The types of analyses presented in this paper are of increasing interest 
to certain Bell System customers because of the increasing number and types 
of services provided over local telephone facilities. 

I. INTRODUCTION 

This report covers the principal results of the 1964 Bell System cus- 
tomer loop survey. This survey provides a statistical characterization 
of physical composition, measured and calculated transmission char- 
acteristics, and measured noise and crosstalk performance of customer 
loop plant. Comparisons of data obtained from the 1964 survey and 
a similar survey made in 1960 are also presented. 

Several of the principal transmission characteristics of Bell System 
customer loop plant as denned by the 1960 loop survey were published 
in 1962 by R. G. Hinderliter. 1 Additional published data on the trans- 
mission characteristics of Bell System toll connections is available in a 
BSTJ article by I. Nasell. 2 

The 1964 Bell System survey was comprised of two separate surveys 
which were merged for analysis and presentation purposes. The basic 
survey was the general loop survey which consisted of a simple random 
sample of 1,100 main stations selected from the population of all main 

3337 



3338 THE BELL SYSTEM TECHNICAL JOURNAL, DECEMBER 1969 

stations (45, 300, 000) as of January 1, 1964. However, since only 3.25 
percent of all main stations are served by loops longer than 30 kilofeet, 
only 35 samples would have been obtained to define the characteristics 
of the longer loops. Consequently, a long loop survey consisting of a ran- 
dom sample of 955 main stations served by loops longer than 30 kilofeet 
was obtained. The data obtained from the long loop survey has been 
used in those instances where characteristics are being expressed as a 
function of length to permit better resolution of the characteristics for 
the longer loops. In both of these sub-surveys, official telephones, foreign 
exchange lines, dial teletypewriter exchange (TWX) lines and special 
service lines were omitted as it was felt that their design would not be 
representative of customer loop plant. 

II. SUMMARY OF RESULTS 

Analyses of data obtained in the 1964 loop surveys lead to six general 
results. 

(i) The average customer loop length is 10.6 kilofeet with only 
10 percent of the main stations located beyond 21 kilofeet from their 
serving office. The length distributions show a slight trend toward longer 
loops between 1960 and 1964, with the average loop length increasing 
by 300 feet. 

(ii) The average 1 kHz insertion loss of Bell System loop plant is 
3.8 dB and 95 percent of all main stations are served by loops having a 
1 kHz loss of less than 8 dB. At 3 kHz, the average loss is 7.8 dB and 
95 percent of the main stations have less than 17 dB insertion loss. 
(in) The average noise balance of party-line loops is 56 dB, while 
the balance for individual line loops is 69 dB. Only 5 percent of the 
individual line loops have a noise balance of less than 50 dB while nearly 
20 percent of party-line customers are served by loops with less than 
50 dB of balance. The substantially lower balance for party lines is 
largely due to the inherent circuit unbalancing effect caused by the use 
of grounded ringers for party-line service. 

(iv) The average metallic circuit noise (C-message weighted) at a 
customer's station set is approximately 5.5 dBrnc including the noise 
contribution of the central office wiring as well the noise contribution 
of the outside plant facilities. Only 8 percent of the individual lines 
have noise in excess of the Bell System objective of 20 dBrnc. However, 
18 percent of the party-line customers have circuits which have noise in 
excess of 20 dBrnc because of the generally poorer circuit balance of 
party-line circuits. 



CUSTOMER LOOP PLANT 3339 

(v) Comparison of measured and calculated transmission char- 
acteristics of Bell System loop plant has demonstrated that the outside 
plant cable records are sufficiently accurate to permit characterizing 
the loop plant transmission performance by theoretical calculations 
based on the physical composition of the loops as described in the outside 
plant records. 

(vi) Main stations served by loops in excess of 30 kilofeet in length 
were found to be exponentially distributed as a function of working 
length, with the population of main stations reduced by 50 percent with 
every 11-kilofoot increase in loop length (see Fig. 6). It is estimated 
that 1.5 million Bell System customers (3.25 percent of all customers) are 
presently served by loops in excess of 30 kilofeet in length. Due to the 
party-line character of longer loops, the 3.25 percent of all Bell System 
main stations included in the long loop segment of plant used only 
1.7 percent of the working Bell System exchange lines. 

III. DESIGN OF THE SURVEY 

The first steps in the survey were to define the population to be 
sampled and to obtain a complete list of the sampling units. In these 
two surveys (that is general loop and long loop), main stations were 
selected as the sampling units and all Bell System main stations as of 
January 1, 1964, were taken as the population to be sampled. A simple 
random sample was chosen as the sampling plan. 

The sample size of the general loop survey was selected to provide 
data of equal precision to that obtained in the 1960 survey. The design 
parameter chosen was the average distance to the sampled main sta- 
tions, and the precision was measured in terms of the width of the con- 
fidence interval bounding this average distance. The desired confidence 
interval (at 90 percent confidence level) of ±450 feet on the average 
cable distance to the sampled main stations dictated a sample size of 
1,100 randomly selected main stations. The actual confidence interval 
obtained was ±476 feet. 

In the long loop survey, lack of previous knowledge concerning the 
composition of long loops made it difficult to accurately determine 
the minimum sample size which would provide sufficient precision. The 
design parameter selected for the long loop survey was the average noise 
metallic (C-message weighting) measured at the telephone sets of the 
sampled main stations to a dialed-up termination. The precision aimed 
for was a ±1.0 dB confidence interval (at 90 percent confidence level). 
A sample size of 955 main stations was collected, and the confidence 
interval obtained was ±0.73 dB. 



3340 



THE BELL SYSTEM TECHNICAL JOURNAL, DECEMBER 1969 



The two surveys had satisfactorily wide geographical dispersion, with 
every associated company (except Canada) contributing to the survey. 
Reference to Fig. 1 will illustrate that the large companies and the 
metropolitan areas contributed heavily to the general loop survey and 
the rural areas contributed heavily to the long loop survey. 

IV. LOOP SURVEY RESULTS — PHYSICAL COMPOSITION 

Data obtained in the loop survey included detailed loop schematics 
indicating the loop composition of each of the loops sampled in the 
survey. All distributions of physical quantities discussed herein were 
derived by analysis of these loop schematics. Since similar data were 
obtained in the 1960 loop survey, comparison of the physical distribu- 
tions obtained in the two surveys has also been made. 

Table I gives a summary of the statistics for the principal physical 
properties of loop plant. Data are included for both the 1960 and 1964 
surveys and significance levels for differences of mean values are pre- 
sented when meaningful. Cumulative distributions of these factors are 
shown in Figs. 2 through 5. The distribution of working bridged tap 
is not given since 82 percent of the sampled main stations were served 
by loops having zero working bridged tap and consequently the dis- 
tribution is not particularly enlightening. 

As indicated in Table I, the estimated average route distance from 
serving central office to main station in the Bell System is 10.6 kilofeet 
with 90 percent confidence that the true mean value lies within ±476 
feet of this estimate. Note that although the estimated mean working 
length in 1964 is over 300 feet longer than that estimated in 1960, it is 
not statistically possible to claim that the observed increase is indeed 



Table I — 1964 Customer Loop Survey Summary 
of Main Station Characteristics 



Main Station 
Quantity 


Mean (ft) 


90% Confidence 
Limits on Mean (± ft) 


Sign. Level for 


1960 


1964 


1960 


1964 


in Percent 


Working length 
Total bridged tap 
Working bridged tap 
Airline distance 
Working length/ 
airline distance 


10,288 

2,619 

381 

7,604 

1.45 


10,613 

2,478 

228 

7,758 

1.50 


450 
169 
107 
353 

0.02 


476 

172 

74 

386 

0.03 


* 
* 

95 

* 

98 



Drop wire excluded except when individual lengths exceed 400 feet. 
* Levels of significance less than 80 percent indicated by asterisk. 



CUSTOMER LOOP PLANT 3341 

an increase. Reference to the cumulative distribution of working length 
depicted in Fig. 3 will, however, show that shifts in the distribution have 
occurred since 1960. Note that the percentage of longer loops increased 
from 1960 to 1964. 

Analysis of the long loop survey data has shown that the Bell System 
main stations served by loops in excess of 30 kilofeet are exponentially 
distributed as a function of working length as depicted in Fig. 6, with 
the main station population (iiminishing by 50 percent with each 11 
kilofeet increase in loop length. Survey analysis indicates that about 
1.5 million or 3.25 percent (with 90 percent confidence interval of 
±0.2 percent) of all Bell System main stations were located 30 kilofeet 
or more from their serving central offices as of the end of 1964. Due to 
the party-line character of the longer loops, the 3.25 percent of all Bell 
System main stations included in the long loop segment of plant used 
only 1.7 percent of the 39,300,000 Bell System lines working in 1964. 

Analysis of the survey data has also provided valuable insight into 
the type-of -service distribution of Bell System customers and the physi- 
cal composition of the plant provided to meet this distribution as shown 
in Figs. 7 to 10. The type-of-service distribution was derived as a 
function of length to the sampled main station and took advantage of 
the pooling of data from the two surveys. To evaluate the physical 
composition (type of facility, gauge, and pair size) of the loop plant as 
a function of distance, the sampled loops from the general loop survey 
were inspected at intervals of 1,000 feet starting at the central office. 
Both the general loop survey and the long loop survey were similarly 
inspected to define these distributions beyond 30 kilofeet. 

The extent of party-line development as a function of loop length 
is shown in Fig. 7. Note the rapid increase in eight-party development 
for loop lengths greater than 30 kilofeet. Examination of the pair size 
distribution as a function of distance from the central office (Fig. 8) 
shows rapidly decreasing pair size with distance (at the 50-kilofoot point 
50 percent of the sampled loops are contained in cables with fewer than 
16 pairs). Similarly, the distribution of gauge shown in Fig. 9 illustrates 
a rapid transition to coarse gauge with increasing distance from the cen- 
tral office. For example, at 30 kilofeet 60 percent of the sampled loops 
are composed of gauges coarser than 22 gauge. Note also (Fig. 10) that 
the longer loops are primarily developed with aerial facilities. For 
example, 78 percent of all plant is aerial at the 30-kilofoot point from the 
central office. For the longer loops where small pair sizes are used, the 
pole line costs become a significant portion of the total loop costs and 
this factor is one of the reasons for the present trend towards the use 



3342 THE BELL SYSTEM TECHNICAL JOURNAL, DECEMBER 1969 

of buried plant. Since the sampled loops were randomly selected from 
all existing plant, buried plant is not as prominent as it would be in a 
sample of new construction. Note, however, that beyond 30 kilofeet, 
buried facilities in 1964 accounted for approximately 20 percent of the 
loops. 

V. 1964 LOOP SURVEY RESULTS — TRANSMISSION PERFORMANCE 

Data obtained in the 1964 loop survey have provided considerably 
more comprehensive knowledge of the transmission performance of 
customer loop plant than heretofore available. In the 1960 loop survey 
all transmission performance data were developed by deriving equivalent 
"T" networks from the information supplied on the loop sketches and 
analyzing these networks for transmission performance at nine fre- 
quencies in the voice band. Similar analysis has been performed for each 
of the sampled loops in the 1964 loop surveys, and in addition trans- 
mission measurements were made. The measurements covered noise, 
crosstalk, insertion loss at 1, 2 and 3 kHz, and dc resistance. The com- 
bination of these two sets of transmission performance data (one cal- 
culated and one measured) permits three types of analysis: 

(i) changes in transmission performance since 1960 by comparison 
of calculated 1960 data with calculated 1964 data, 

(m) comparison of measured versus calculated data for the 1964 
survey, and 

(Hi) provision of heretofore unavailable data on the noise and cross- 
talk performance of customer loop plant. 

Since measured insertion loss data was not obtained in the 1960 
survey, comparison of 1960 and 1964 data must be based on calculated 
values. Figure 11 depicts the 1 kHz calculated distributions for both 
surveys. It can be seen that insertion loss performance has remained 
virtually unchanged since 1960. 

For those transmission characteristics where measured data are 
available in addition to the analytically derived data, minor differences 
in performance are exhibited by the two distributions of data (Fig. 12). 
In this regard it is important to realize that the measured data should 
provide a more accurate estimate of performance. There are several 
reasons for greater confidence in the measured data. First, possible in- 
accuracies in cable records or errors in transferring data from the records 
to the loop sketches can introduce errors in the calculated data. Second, 
errors in construction, such as omission or improper connection of load- 
ing coils, cannot be detected from the records. Third, use of calculated 



CUSTOMER LOOP PLANT 3343 

data assumes that all cables exhibit nominal characteristics and con- 
sequently do not reflect manufacturing tolerances and environmental 
factors. 

The cumulative distributions of insertion loss at 1, 2, and 3 kHz for 
customer loop plant as derived from both measured and calculated 
data are presented in Fig. 12. These insertion loss measurements and 
calculations were made with a 900 ohm source and load as depicted in 
Fig. 13. Measured loss was found to be consistently higher than calcu- 
lated loss across the entire voice frequency band. The absolute dif- 
ferences between measured and calculated losses are small however, as 
indicated by the differences in mean losses. For example, at 1 kHz the 
measured loss was 3.8 dB and the calculated loss was 3.5 dB. This com- 
parison of measured and calculated insertion losses demonstrates the 
feasibility of characterizing the loop plant transmission performance by 
theoretical calculations based on the physical composition of the loops 
as described by outside plant records. Still referring to Fig. 12, note 
that approximately 95 percent of all Bell System main stations are 
served by loops having a 1 kHz insertion loss of less than 8 dB with a 
mean loss of 3.8 dB. Similarly, at 3 kHz the 95 percent point is 16 dB 
and the mean loss is 7.8 dB. A scatter diagram of the 1 kHz measured 
insertion loss as a function of loop length is shown in Fig. 14. This dia- 
gram was obtained by merging the data from both the general loop 
survey and the long loop survey and indicates that the high loss loops are 
not limited to the long loop category. The high losses observed on some 
of the short loops generally reflect excessive bridged tap. 

An insertion loss measurement of particular interest to designers 
of data equipment is the slope of loss versus frequency from 1000 to 
2750 Hz. Cumulative distributions of the 2750 - 1000 Hz insertion 
loss (insertion loss measured with 900 ohm source and load) have been 
provided for all Bell System loop plant and for those loops serving 
business customers in Figs. 15 and 16 respectively. 

Another important transmission characteristic is return loss, signifi- 
cant from echo and singing considerations. Return loss performance was 
not available from the measured data; consequently, it was cal- 
culated. Table II provides 1964 loop survey return loss results for nine 
frequencies and Fig. 17 presents the cumulative distributions and 
histograms for the 3 kHz singing return loss and echo return loss (equal 
weighting of the 500 to 2,500 Hz band). These data are all developed 
on the basis of looking into the customer loop at the central office end 
of the loop. The return loss is obtained by matching against a 900 ohm, 
2.16 jiF termination at the central office, with the customer end of the 



3344 



THE BELL SYSTEM TECHNICAL JOURNAL, DECEMBER 1969 



Table II — Calculated Return Loss From Office 
Toward Station* 





1964 






90% Confidence 


Frequency (Hz) 


Mean (dB) 


Interval (± dB) 


200 


8.0 


0.11 


300 


10.2 


0.12 


500 


13.4 


0.17 


1,000 


15.4 


0.30 


1,500 


13.1 


0.27 


2,000 


10.9 


0.25 


2,500 


9.1 


0.20 


.'5,000 


7.7 


0.16 


3,200 


7.1 


0.15 


Echo 


11.2 


0.15 



Station end of loop terminated in impedance of "off-hook" station set. 



loop terminated in the impedance of the "off -hook" station set. Similar 
data on return loss are presented later from the station end of the loop. 

The comparison of measured versus calculated loop resistance shown 
in Fig. 18 indicates that for general loop plant there is no significant 
difference between measured and calculated data but calculated loop 
resistance is slightly higher than measured resistance (574 ohms cal- 
culated, 567 ohms measured). Measured values may have been in- 
fluenced by the fact that measurements were made during the winter. 
Calculated resistances were based on an average temperature of 68°F. 

Theoretical calculations cannot be made of all transmission perform- 
ance characteristics. Two such examples are noise and crosstalk. Since 
these characteristics are dependent upon external influences (induction 
from adjacent power lines, cable pair balance and the particular pair 
assignment), field measurements were made on each of the sampled 
loops using a Western Electric Company model 3A noise measuring set. 
The noise and crosstalk measurements were made as depicted in Figs. 
19 and 20. 

It is convenient to analyze loop noise in terms of the two factors 
which contribute to the resultant interference. The first of these is the 
magnitude of open circuit longitudinal voltage induced from power 
lines and the second is the circuit balance of the cable pairs and central 
office equipment. The cumulative distribution of the open circuit longi- 
tudinal voltage for general loop plant is shown in Fig. 21 for 3 kHz flat 
weighting. This voltage is induced in a longitudinal mode, and conse- 
quently only that portion of it which is converted to the metallic circuit 



CUSTOMER LOOP PLANT 3345 

will create an interference problem. The circuit balance reflects the 
extent to which the longitudinal voltage is converted to metallic voltage 
and is, therefore, a measure of the susceptibility of the telephone plant 
to inductive interference such as power-line hum.* 

As seen in Fig. 22 party lines are much more susceptible to power- 
line hum than individual lines because of the unbalance introduced by 
the grounded ringers associated with party-line station sets. On the aver- 
age, individual lines have approximately 12 dB better balance than party 
lines. Part of this is a result of the shorter length distribution of in- 
dividual lines which offers less opportunity for cable pair unbalances 
to accumulate; but it is reasonable to expect a balance improvement of 
10 dB with ringers isolated from ground. 

The combination of the induced longitudinal voltage and the circuit 
unbalance produces the metallic noise distribution at customers' station 
sets (in off-hook state) as shown in Figs. 23 and 24. For comparison 
purposes, the C-message weighted noise to ground (longitudinal noise) 
is also shown on these figures. Figure 23 depicts the noise contribution 
of the loop plant only, while Fig. 24 includes the noise contribution of 
the central office wiring. In both cases the station end of the loop was 
terminated in an off-hook 500-type station set with the transmitter 
and receiver replaced by equivalent resistors. The metallic noise has been 
measured with C-message weighting to reflect the relative interfering 
effects of the noise on voice transmission. The important limits to con- 
sider are the Bell System long-term noise performance objective of 20 
dBrnc and the immediate remedial action limit of 30 dBrnc. As seen 
in Fig. 24, only 8 percent of the individual lines had total metallic 
noise in excess of 20 dBrnc. However, 18 percent of the party-line cus- 
tomers have noise in excess of 20 dBrnc. 

The near-end crosstalk coupling loss characteristics of customer loop 
plant as derived from measured data from the general loop survey are 
shown on Fig. 25. Along with the overall distribution of crosstalk 
coupling loss is shown the distribution for nonloaded loops only (84 
percent of all sampled main stations) . The nonloaded loop distribution 



* Loop circuit noise balance is defined here as 

9n . open circuit longitudinal voltage 

metallic voltage 

where both voltages are measured with C-message weighting. The validity of this 
definition depends on the assumption that the longitudinal voltage induced from 
adjacent power lines is the only source of metallic noise. This is generally not true 
when the noise to ground measures less than 20 dBrnc, and consequently loop 
balance for such loops cannot be computed from the measurements. 



3346 THE BELL SYSTEM TECHNICAL JOURNAL, DECEMBER 196t) 

can be approximated by a normal distribution with a mean crosstalk 
coupling loss of 115 dB and a standard deviation of 12 dB. A comparison 
of these two curves indicates that the poorer crosstalk performance of 
longer loaded loops dominates the low loss tail of the general loop survey 
distribution. 

The final transmission characteristic to be discussed is the loop input 
impedance as calculated both at the central office and at the station set. 
Figure 26 presents the plot of loop input impedance as seen at the 
central office as a function of frequency (not including central office 
wiring or equipment). For these calculations the station end of the 
loop was terminated in an off-hook 500-type station subset with the 
transmitter and receiver replaced by equivalent resistors. Curves have 
been provided separately for loaded and nonloaded loops because of 
the large difference in their characteristic impedance. Also shown is the 
characteristic impedance of the central office matching network as a 
function of frequency. The function of this network is to provide high 
return loss performance across the voice frequency band by matching 
as close as possible the impedance of the various loops. It is apparent 
that both the nonloaded loops and loaded loops should have their 
highest return losses around 1 kilohertz and that the loaded loops 
should perform more poorly than nonloaded loops at the lower fre- 
quencies. 

Plots of mean input impedances, such as in Fig. 26, are useful for 
indicating the general input impedance behavior as a function of fre- 
quency. Variations that occur at each frequency, and their effects on 
return loss, are best shown as scatter diagrams. Figures 27 and 28 
present the loop input impedance at 1 kHz for nonloaded and loaded 
loops. Superimposed on all scatter diagrams are return loss circles 
referenced to the 900 ohm and 2.16 /jF matching network. Any loop 
having an impedance lying within a particular circle will have a return 
loss, when measured against the specified matching network impedance, 
which exceeds the given return loss value. Visual examination of the 
scatter pattern as it relates to the return loss circles provides a ready 
means of evaluating the return loss performance of various segments of 
the loop plant (assuming, of course, that the input impedances of loops 
in that segment are known). 

The range and shape of the input impedance scatter pattern at each 
frequency are of interest because they point up the difficulty of designing 
a simple matching network which, at even a single frequenc3 r , will 
provide very high return losses for nearly all loops. Considering the 
characteristics of the nonloaded loops shown in Figure 27 it is evident 



CUSTOMER LOOP PLANT 3347 

that many of the loops tend to follow a smooth curve, while the others 
are scattered about this curve. The smooth curve results from the varia- 
tion in loop length, while the scatter is due to the effects of bridged tap, 
overgauging, and variations in types of subsets. 

Perhaps of particular interest to Bell System customers are the input 
impedance characteristics of Bell System loop plant as seen from the 
station end of the customer loop. The input impedance of a customer 
loop as measured at the station set can vary considerably based on the 
type of facility connected to the loop at the central office. Various cir- 
cuit connections may involve use of four-wire trunks, two-wire trunks 
or intraoffice circuits. In the following analysis a 900 ohm and 2.16 nF 
central office termination has been used to represent a four-wire trunk 
termination, and the midsection input impedance of 22 gauge H88 
loaded cable has been used to represent a two-wire trunk. For the simula- 
tion of intraoffice calls, a Monte Carlo technique was used to select a 
random sample of 500 pairs of loops from the 1,100 loops in the general 
loop survey. A loop was randomly selected as the sample loop, and then 
the input impedance (from the central office) of another randomly 
selected loop was chosen for the central office termination. 

The 1,100 loops of the 1964 general loop survey were segregated into 
two groups (loaded and nonloaded loops) for all but the simulated 
intraoffice calls because of the great differences in impedance range of 
the two populations. Presentation of scatter diagrams of input im- 
pedance from the station set has been limited to 1 and 3 kHz. These 
return loss circles were generated assuming the use of a 500-type station 
set and it was further assumed that the 500 set was operating on a cur- 
rent equal to the average loop current of 45.5 mA. 

Figures 29 through 32 are the input impedance scatter diagrams for 
loops with a simulated two-wire trunk (22 gauge H88 loaded cable) 
termination at the central office. The scatter is primarily a result of 
overgauging, open wire, and bridged tap or varied end section length. 
Smoothed curves of the mean input impedances of loaded and non- 
loaded loops with a 22 gauge H88 cable termination are presented in 
Fig. 33. Scatter diagrams for the loops with a central office termination 
of 900 ohms and 2.16 nF (simulated four-wire trunk) are presented in 
Figs. 34 through 37. The general input impedance behavior of these 
loops as a function of frequency is indicated in Fig. 38 by the plot of the 
mean input impedances at nine voiceband frequencies. 

The scatter diagrams and the mean input impedance curve for the 
simulated intraoffice calls are shown in Figs. 39 and 40. The effect of 
connecting together two loops, one of which is terminated by a station 



3348 THE BELL SYSTEM TECHNICAL JOURNAL, DECEMBER 1969 

set, and the other whose input impedance is calculated at its station 
set, is shown by the mean input impedance curve for simulated intra- 
office connections in Fig. 41. This curve has a shape characteristic of 
longer nonloaded loops. The mean input impedance curves for non- 
loaded loops with simulated two- and four-wire trunk terminations at 
the central office are also shown in Fig. 41. The major differences in the 
characteristics of these curves are at the low frequencies where the shunt 
capacitance of the cable masks the termination less than it does at high 
frequencies. 

VI. ACKNOWLEDGMENTS 

The author wishes to acknowledge the collaboration of Mr. F. L. 
Schwartz in the design and execution of this Bell System customer loop 
survey and his analysis of noise and crosstalk characteristics of loop 
plant. I also want to thank Mrs. A. F. Rogers for the substantial pro- 
gramming assistance required in the analysis of the data obtained in 
this study and Mr. D. B. Menist and Mrs. B. J. Hymanson for their 
contributions on the input impedance characteristics of loop plant. 

REFERENCES 

1. Hinderliter, R. G., "Transmission Characteristics of Bell System Subscriber 

Loop Plant," AIEE Summer General Meeting, Denver, Colorado, June 
17-18, 1962, Paper 62-1198. 

2. Nasell, I., "Some Transmission Characteristics of Bell System Toll Collec- 

tions," BJ3.T.J., 47, No. 6 (July-August 1968), pp. 1001-1018. 



CUSTOMER LOOP PLANT 



3349 



34-14 




Fig. 1 — Geographic distribution of sampled loops for the 1964 customer loop 
survey. Eleven hundred loops were sampled for the general loop survey and 955 
loops were sampled for the long loop survey. 



3350 THE BELL SYSTEM TECHNICAL JOURNAL, DECEMBER 1969 



20 











-C^" 


^ — — - 














I96C 


//196 


4 
















/ 




















/ 






































ll 
II 
II 




















ll 
ll 
II 
ll 


















f\ 




















It 
ll 
II 
II 









































20 25 30 

LENGTH IN KILOFEET 



35 



40 



4 5 



Fig. 2 — Working length to the main station. 

1960 1064 

Mean (feet) 10,288 10,613 
90 percent confidence 

limits on mean (feet) ±450 ±476 



CUSTOMER LOOP PLANT 



3351 



(00 



z 70 

o 



.?. 40 









1964 


•""i960 
















/" 


















/ 




















/ 











































































































































6 8 10 12 14 

LENGTH IN KILOFEET 

Fig. 3 — Total bridged tap. 



Mean (feet) 
90 percent confidence 
limits on mean (feet) 



1960 
2,610 

±169 



1964 

2,478 

±172 



3352 



THE BELL SYSTEM TECHNICAL JOURNAL, DECEMBER 196S) 



60 







• 


^ 


.— •— ' •"" 














19 


60//19 
/ / 


S4 
















f 
1, 

if 








































A 
h 


















J 


i 

i 
i 

1 


















II 
II 
II 




















II 
ll 
II 
II 




















ll 
II 









































5 10 15 20 25 30 35 40 

LENGTH IN KILOFEET 

Fig. 4 — Airline distance to main station. 

1960 1964 

Mean (feet) 7,604 7,758 

90 percent confidence 

limits on mean (feet) ±353 ±386 



CUSTOMER LOOP PLANT 



3353 



iOO 




1.4 1.6 1.8 2.0 2.2 2.4 2.6 

RATIO OF WORKING LENGTH TO AIRLINE DISTANCE 



Fig. 5 — Ratio of working length-airline distance to main station. 

1960 1964 

Mean 1.45 1.50 

90 percent confidence 



limits on mean 



±0.02 



±0.03 



3354 



THE BELL SYSTEM TECHNICAL JOURNAL, DECEMBER 1969 




I.SXIO 6 



(50,000 $5 



15,000 



70 90 110 130 150 170 190 

LENGTH TO MAIN STATION IN KILOFEET 



210 



Fig. 6 — Distribution of long loops (1964 long loop survey). The mean was 
45,938 feet; 90 percent confidence limits on the mean was ±870 feet. 



CUSTOMER LOOP PLANT 



3355 




16 20 24 28 32 36 40 

LENGTH TO MAIN STATION IN KILOFEET 



Fig. 7 — Type of service distribution versus loop length (1964 combined loop 
surveys) . One-, two-, four-, and eight-party plots include residence service only ; 
business includes PBX, centrex, and coin. 



3356 



THE BELL SYSTEM TECHNICAL JOURNAL, DECEMBER 1969 



E 60 

< 
tfl 

O 50 



£ 40 





















^3 


" / 

/ ° 


O / Q 


/ >/ 

? / & 
















/ ^ 


/ OS / 

/ / 
/ / c 

/ > 








' / 








' / 






* / 




•^ / 










A 








/ ' 


A/ ' ^ A 








II 




















Hi 




















II 




















// 









































20 30 40 50 60 70 80 

DISTANCE FROM CENTRAL OFFICE IN KILOFEET 



90 



Fig. 8 — Pair size distribution (1964 combined loop surveys— general loop and 
long loop surveys). 



CUSTOMER LOOP PLANT 



3357 




20 30 40 50 60 70 80 

DISTANCE FROM CENTRAL OFFICE IN KILOFEET 



Fig. 9. — Gauge distribution (1964 combined loop surveys— general loop and 
long loop surveys) . 



3358 



THE BELL SYSTEM TECHNICAL JOURNAL, DECEMBER 1969 



100 


































































60 
50 






























































30 


















S \OPEN WIRE 
















AERIAL 


RURAL 


-URBAN 
RE 


















CABLE 






10 



UNDERGROUND } 
CABLE 


BURIED 
CABLE 





























10 20 30 40 50 60 70 80 90 100 

DISTANCE FROM CENTRAL OFFICE IN KILOFEET 

Fig. 10 — Type of construction distribution (1964 combined loop surveys — 
general loop and long loop surveys) . 



CUSTOMER LOOP PLANT 



3359 



« 80 
O 



O 40 









ikHz 








^ 














/ 


2 KHz 
/y 

/ 


3 kHz 














ft 


// 

// 


/ 


f 














ji 


' A > 


// 
y 


















J 


Y 





















8 10 12 14 

INSERTION LOSS IN DECIBELS 



Fig. 11 — Distribution of calculated insertion losses at 1, 2, and 3 kHz 





nfidence 
jan (dB) 


1kHz 


2 kHz 


3 kHz 


Mean (dB) 
90 percent co 
limit on m 


1960 1964 
3.4 3.5 

±0.11 ±0.10 


1960 1964 
5.4 5.3 

±0.18 ±0.16 


1960 1964 
7.4 7.3 

±0.24 ±0.21 



3360 



THE BELL SYSTEM TECHNICAL JOUENAL, DECEMBER 1969 




6 8 10 12 14 16 

INSERTION LOSS IN DECIBELS 



Fig. 12 — Distribution of measured and calculated insertion losses at 1, 2, and 
3 kHz ( calculated; measured). 



1 kHz 

Meas- Calcu- 

ured lated 



2 kHz 
Meas- Calcu- 
ured lated 



3.8 



3.5 



5.6 



5.3 



Mean (dB) 

90 percent confidence 

limit on mean (dB) ±0.12 ±0.10 ±0.17 ±0.16 



3 kHz 

Meas- Calcu- 

ured lated 

7.8 7.3 

±0.22 ±0.21 



CENTRAL OFFICE 




OUTSIDE PLANT 



Tf 



CUSTOMER 
LOOP TO BE 
MEASURED 



ON -HOOK 
STATION SET 




3A NOISE 
MEAS. SET 



Fig. 13 — Insertion loss measurement technique. The oscillator is set for 600 
ohm output termination; the 3 A noise measurement set is equipped with 900 
ohm termination. 



CUSTOMER LOOP PLANT 



3361 



lb 












































12 

Ul 

_i 

UJ 
CD 








"*■•."■ ' 




•.-'• ' ' 










UJ 

Q 

Z 








*. .'. . 


7" 


.MEAN 
• LOSS 


C^ 








g 8 
O 








'.t ' ' 


.', . . . 














• ':.• 




t .' X ". J 














z 
o 

fe 6 

UJ 

m 
Z 




'.'"•:.'■ ■ 


•■•Z^^""" 


ti!fc. a l" 


v,vy.*; : 












.V-. 


w« 


1 . 




• :•'•■'■ 
















2f ' " 




::..-.. 














2 


i .' /Vii'"~ 




















"JR* 























p 7 - • 





















30 40 50 60 70 80 

LENGTH TO MAIN STATION IN KILOFEET 



Fig. 14 — Measured 1 kHz insertion loss scatter diagram (1964 combined loop 
surveys — general loop and long loop surveys). 



3362 



THE BELL SYSTEM TECHNICAL JOURNAL, DECEMBER 19(59 



100 



O 50 





























c 


J/"^ 


























A 
















/ 














/ 














/, 


/ 














/ 














11 


/ 

> 














1 
















1 

















I 2 3 4 5 6 7 

INSERTION LOSS SLOPE IN DECIBELS 



Fig. 15 — Distribution of insertion loss slope between 2750 and 1000 Hz for 
residential plus business loops. 






CUSTOMER LOOP PLANT 



3363 



o 

H 40 

z 













^•^i 


























/ 














I 


/ 














/ 
















/ 
















1 































































2 3 4 5 6 7 

INSERTION LOSS SLOPE IN DECIBELS 



Fig. 16 — Distribution of insertion loss slope between 2750 and 1000 Hz for 
business loops only. 



3364 



THE BELL SYSTEM TECHNICAL JOURNAL, DECEMBER 1969 



(/i 70 

Z 

o 



30 



20 



10 



















7\ \ 














ECHC 


RET 


JRN I 


-OSS, 




At 


<HZ F 


*ETUF 


N LC 


SS 




















/ 






























/ 




























/ 




























/ 


/ 




























/ 


























/ 






























/ 


/ 


























s 


/ 


J 

























10 12 14 16 18 20 
RETURN LOSS IN DECIBELS 



22 24 26 28 30 



Fig. 17 — Distribution of 3 kHz and echo return losses at central office. Echo 
return loss distribution assumes flat weighting of 500-2500 Hz band. 



Mean (dB) 
90 percent confidence 
limits on mean (dB) 



Echo 
7.7 

±0.16 



3 kHz 
11.2 

±0.15 



CUSTOMER LOOP PLANT 



3365 



100 



t- 60 

4- 
< 

5 50 

u 
o 

H 

.?. 40 



30 



20 





























MEASUR 


ED— J/ 


•-CALCULATED 














w 
















/ 



































































































































400 600 800 1000 1200 1400 (600 

RESISTANCE TO MAIN STATION IN OHMS 



1800 2000 



Fig. 18 — Measured and calculated distribution of resistance to main station. 

Measured Calculated 

Mean (ohms) 

90 percent confidence 



limits on mean 



567 
±15.8 



574 
±17.0 



3366 



THE BELL SYSTEM TECHNICAL JOURNAL, DECEMBER 1969 




OUTSIDE "OFF-HOOK" 500-TYPE 

PLANT SET WITH TRANSMITTER 

AND RECEIVER REPLACED 
BY RESISTORS 



7T 



CUSTOMER 

LOOP TO BE 

MEASURED 




3A 
SET 



900 n 

TERMINATION 



900 a 

TERMINATION 



CUSTOMER 
LOOP TO BE 
MEASURED 



3A 
SET 



X 



Fig. 19 — Noise measurement technique for (a) noise metallic — loop only and 
(b) noise longitudinal — loop only. 



CUSTOMER LOOP PLANT 



3367 




OUTSIDE "OFF-HOOK" 500 -TYPE 

PLANT SET WITH TRANSMITTER 

AND RECEIVER REPLACED 
BY RESISTORS 






CUSTOMER 

LOOP TO BE 

MEASURED 




3A NOISE 900 O. 

MEAS. SET TERMINATION 



"OFF- HOOK" 
STATION SET 



Tt 




DISTURBING 
LOOP 



Fig. 20 — Crosstalk measurement technique. Disturbing loop — randomly se- 
lected pair in the same 100-pair group as the sample loop on which the measure- 
ments are being made. The oscillator on disturbing loop is set for 600-ohm 
output termination. 



3368 



THE BELL SYSTEM TECHNICAL JOURNAL, DECEMBER 1969 



z 
o 



i- 
?, 40 



o 




34 42 50 58 66 74 8 2 90 

0.1 1 5 10 25 50 

NOISE TO GROUND (3A NOISE MEASURING SET READING) 



Fig. 21 — Noise to ground at main station for 3 kHz flat weighting. The mean 
was 49.2 dBrn; the 90 percent confidence limits on the mean was ±0.56 dBrn. 



CUSTOMER LOOP PLANT 



3369 





20 



44 50 56 62 68 

LOOP BALANCE IN DECIBELS 



92 



Fig. 22 — Loop circuit noise balance. These distributions are based on the 476 
loops where measurements permitted an accurate estimate of loop balance to be 
made. These are for loops having noise to ground greater than 20 dBrnc. 



Mean (dB) 
90 percent confidence 
limits on mean (dB) 



Party 
56.1 

±1.55 



Individual 
6877 

±0.87 



3370 



THE BELL SYSTEM TECHNICAL JOURNAL, DECEMBER 1969 



100 






















if) 80 

Z 






















5 

z 
< 


INDIVIC 
LINE 


UAL 
S ~^y 










j£ NOISE TO GROUND 
f^~~~ (LONGITUDINAL) 








/ 


' \ 














LL 

°40 

\- 
z 

LLI 
O 




' \ 


/ 


PARTY 
LINES 
















ALL 

LINES 

/ 


Z 
















a. 20 


































































-12 



6 12 18 24 30 

NOISE METALLIC IN dBmC 



42 



48 



Fig. 23 — Noise metallic at main station with C-message weighting for loop 
plant only. 

Noise Metallic 

Noise to — 

Ground All Individual Party 

Mean (dBrnc) 19.1 -1.1 -3.1 ' 6.7 

90 percent confidence 

limits on mean (Bdrnc) ±0.5 ±0.5 ±0.5 ±1.3 



CUSTOMER LOOP PLANT 



3371 




-12 



-6 



6 12 18 24 30 

NOISE METALLIC IN dBlTIC 



36 



42 



48 



Fig. 24 — Noise metallic at main station with C-message weighting for loop 
plant plus central office. 



Noise Metallic 



Mean (dBrnc) 

90 percent confidence 

limits on mean (dBrnc) 



Noise to 

Ground 

19.1 
±0.5 



All 
5.6 

±0.5 



Individual 
4.3 

±0.6 



Party 
10.6 

±1.2 



3372 



THE BELL SYSTEM TECHNICAL JOURNAL, DECEMBER 1969 



(S 99.99 



























<; 


















































































































































































SN 


^,-ALL LOOPS 












NO 
LOC 


NLOAC 

ips or 


ED 

JLY 


-"" 'v 





































110 105 100 95 90 85 80 75 70 

NEAR END CROSS TALK COUPLING LOSS IN DECIBELS 



Fig. 25 — 1 kHz near end crosstalk coupling loss at central office. Central of- 
fice terminated in 900 ohms; customer end terminated in receiver off hook sta- 
tion set. 




-600 



400 



600 



1000 1200 1400 1600 

RESISTANCE IN OHMS 



1800 2000 2200 



Fig. 26 — Loop impedance at central office. 



CUSTOMER LOOP PLANT 



3373 



200 


/ 


/ 


/ 


/./ 


/ 
















\ 






/ 


/ 


%/" 


'%?'■•; 




• • ;•: 












\ 
















K ". .-• 


I • * 


• /*.' 
















\ 






"_.■ 




"" t 


.'■ < 










in 

5 






\ 


\ 










■ / 










z 








V 


\I2 


dB • 








.* •!•••■ 








z 

U -500 
UI 










jodB 


































• ,\* & 


/". 






y 




\ 8 dB .• v 












\60 


B "^ 


...■*.•'% 


:"•& 


•^ 


■}■ ' '• 




'-' 












i4dB 








■*•' * 


; ; ! \; 


' * » s 


























. • ■ 


•' 








































-1000 









200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 
RESISTANCE IN OHMS 



Fig, 27 — Nonloaded loop input impedances at 1 kHz measured from the cen- 
tral office. Return loss circles based on 900 ohm + 2 juF network. 



3374 THE BELL SYSTEM TECHNICAL JOURNAL, DECEMBER !969 



o 

z 

uj o 

o 

z 

o 

< -200 

UJ 

cr 



-400 









AdB 


/edB 


/adB 


















/ 










odB^ 








// 




y\zt 


JB * 












// 


7/ 




























. 












\\ 




t 


v. 


•; 




/ 




\ 






*-■*"■■— ii 


-"• - 


<S\ . 


/ 


/ 




\ 


V 








■ • 




/ 



200 400 



600 800 1000 1200 1400 1600 1800 

RESISTANCE IN OHMS 



Fig. 28 — Loaded loop input impedances at 1 kHz as measured from the 

central office. Return loss circles based on 900 ohms + 2 jiF network. 



CUSTOMER LOOP PLANT 



3375 



100 


w 


\ \ 


\ 
























V 


\\ 
























-100 




W 


N 


\ 














. 






-200 




\ 


\\ 


\ 


s 














7^ 




-300 




— ^ 


\\ 














• 


•'"■■•V 






m 




. ••% 


I 

o 

?-500 






:N 












t •. ■ 


I*??* 


L "•" 












%;.:■•: 


&;: 


^ 




• .-' : 






N .. 


5 




<J 








< 

o 








•^ 




fflxA 




'$£'.'; 


• . s 


•v • 








a 












■>M 




fev:; 


>** ••• 
































3 
























v2 










-1100 














\1 















100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 
RESISTANCE IN OHMS 

Fig. 29 — Nonloaded loop input impedances at 1 kHz measured from station 
set with a simulated two-wire trunk termination at the central office. Return loss 
circles based on 500-type subset impedance. 



3376 



THE BELL SYSTEM TECHNICAL JOURNAL, DECEMBER 1909 



-100 



-200 



-30C 



-400 



uj-500 
U 

z 
< 

a: 



600 



-700 

-800 

-900 

-1000 
-1100 



\ 


\ 


y 


\ 




















\ 


\\ 


\ 


\ 




















• \ 


■\\ 

i A. 


■ \ 

V 




\ 




















M 


&- 


•\ 


\ 


V 


















S?" A 






\ 


nJ 






























s7 














?w.. 




















- 












'a 










\5 




















\ 1 
MS 




























v ' .4, 


\ 3 






















\i 


\2 




^". J 




y'- .••: 


• 

































100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 

RESISTANCE IN OHMS 



Fig. 30 — Nonloaded loop input impedances at 3 kHz measured from station 
set with a simulated two-wire trunk termination at the central office. Return 
loss circles based on 500-type subset impedance. 



CUSTOMER LOOP PLANT 



3377 



200 
100 



-200 



O -300 



w -400 



-800 



-900 



-1000 





























y\ 


























\\ 


























ss 
























/ 




\\ 




















7^" 






\\ 


X 










' ~ 


•1 — ^ 
















\/' 








1 
















V 


V 


^v 


.' . t 


\' " 


"is*""" 


-• — : 




5 










\ 








' 




















\ 








9^3 


















^ 


\ 




v2 






















K 


\ 

















00 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 
RESISTANCE IN OHMS 

Fig. 31 — Loaded loop input impedances at 1 kHz measured from station set 
with a simulated two-wire trunk termination at the central office. Return loss 
circles based on 500-type subset impedance. 



3378 



THE BELL SYSTEM TECHNICAL JOURNAL, DECEMBER 1969 





\\ 


\ 


v 


V 




















V 


\\ 


\ 


\ 




















\ 


\\ 


• \ 


\ 


>, 






















\ '. \ 


\ 


\ 




















12 -/nn 






v 


V 




















i 
O 

Z -500 




■•■\ 

* • 


V'\ 


\ 








S^7 


















\ ^ 


















. 


UJ 














■k 








5 s 














E 








































3 


\ 
























\ 


2\ 




\ 












-1100 










\ 




\ 




\ 


">• 









O 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 

RESISTANCE IN OHMS 

Fig. 32 — Loaded loop input impedance at 3 kHz measured from station set 
with a simulated two-wire trunk termination at the central office. Return loss 
circles based on 500-type subset impedance. 



2 -500 



? -600 































320 


DHZ 




2 

(A 


500 H 7 
"200C 


Lfl. 

H7, 


qIOOO 


HZ 














320 


HZd 


ap<o 






N 


L LOADED 
\ 1 

>q500 H 


Z, 
















100 


HZ 
NO 


•JLOAD 


ED* 

500 V 




























\ 


^S 
























20C 


HZ*> 


\ 





























-1000 

100 200 300 4CO 500 600 700 800 900 1000 1100 1200 1300 

RESISTANCE IN OHMS 

Fig. 33 — Mean value of loop input impedance from station set with simu- 
lated two-wire trunk termination at the central office. 



CUSTOMER LOOP PLANT 



3379 



-200 



uj -500 



U -600 



-900 



w 




\ 






















~v 




\ 
























\\ v 


\ 
























\ v 


\\ 














*""•.."" 












\\ 


















7 








\ 


\ • 


X 








* . k ; 




.» 












^- ,] 


^8 


v.-. 




;*S- 


" "****•■< 




• 5 




















^ 




ftsl 


*■■>•)•■ 


*•!■ * *- * * 






















*'••* 


-.^...s 




























s^a 




















V 


2\ 
























\ 





\ 


N 









100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 
RESISTANCE IN OHMS 



Fig. 34 — Nonloaded loop input impedances at 1 kHz measured from station 
set with simulated four-wire trunk termination at the central office. Return loss 
circles based on 500- type subset impedance. 



3380 



THE BELL SYSTEM TECHNICAL JOURNAL, DECEMBER 1969 



200 



uj-400 

u 

z 

g-500 
< 



in 



-600 



-1000 



\V 


, \ 


\ 






















\\ 




\ ' 


V 






















\ 


\ 


\ 






















{ -'v 


■\ 
r 


\ 

V 






















i% 


k 


\ 




















■ V.-i 




: \ 
fe." 


\ 


















\ 


■>\1 *n 




\ 


K • 


. .•; 


<• 
















\ ^ 


" ' •""'•£■ V 


••i-S:' 


N s 










. 




7 














































v^S 


















S* 


\3 






















\ 


\ 

















100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 

RESISTANCE IN OHMS 



Fig. 35 — Nonloaded loop input impedance at 3 kHz measured from station 
set with simulated four-wire trunk termination at the central office. Return loss 
circles based on 500-type subset impedance. 



CUSTOMER LOOP PLANT 



3381 



200 




\ 
























100 




A 






























V 



















































5 






\\ 


















7, 




o 300 






\\ 






















2 








uj -400 

2 
< 






\ 










S- * 












G soo 
< 








V 


Y 


•\. 






*"*"■• 




5 






a. 
















\ 


• ;S 




• *i<L 














-700 


















,3 






















\1 


2\ 














-tooo 














\ 












^^- 



RESISTANCE IN OHMS 

Fig. 36 — Loaded loop input impedances at 1 kHz measured from station set 
with simulated four-wire trunk termination at the central office. Return loss 
circles based on 500-type subset impedance. 



3382 



THE BELL SYSTEM TECHNICAL JOURNAL, DECEMBER 1969 



-200 



-300 



5 
I 
O 

? -500 



< -600 

1- 

S 

8 -700 



\\ 




\ \ 






















\ 






\ 




















\ 


Y 




s s 




















\ 


\;'\ 


























.'•A 


W 




\ 




















• * 


^ 




\ 






















v .. 























7 










:v\ 






















_ 








\ 










^5 
















\ 


\ • 


\ 






















\ 


\ 




\3 




















\ 




V 




"N 











-1100 

tOO 200 300 400 500 600 700 800 900 1000 1100 1200 1300 

RESISTANCE IN OHMS 

Fig. 37 — Loaded loop input impedances at 3 kHz measured from station set 
with simulated four-wire trunk termination at the central office. Return loss cir- 
cles based on 500-type subset impedance. 



-300 




100 2O0 300 400 600 600 700 800 900 1000 1100 1200 1300 1400 
RESISTANCE IN OHMS 



Fig. 38 — Mean value of loop input impedance from station set with simulated 
four-wire trunk termination at the central office. 



CUSTOMER LOOP PLANT 



3383 



100 



-200 



-300 



If) 

O "400 






A 
























\\ 


\ 














• 










\Y 


N 

\ 












•• 




. 






y 


\ 


\\ 




















7^ 








\ 




















































X-;- 


& 


• • \ 














5 


— 












\ 






»'•" " . v 


•■■ 






















' '-N.' 




•<X 






















\ 


























\ 


S, 


\ 


\ 








L3 














\ 




\ 


^ 











-700 

-800 

-900 

-1000 

-1100 

100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 

RESISTANCE IN OHMS 

Fig. 39 — Input impedance of all loops at 1 kHz measured from station set 
with a simulated intraoffice circuit termination at the central office. Return loss 
circles based on 500-type subset impedance. 



3384 



THE BELL SYSTEM TECHNICAL JOURNAL, DECEMBER 1969 



200 



-100 



-200 
| -300 

! -400 

I 

! -500 

I -600 
I 

-700 
-800 
-900 
-1000 



\Y 


y\ 


V 






















\\ 




y : 


v 






















\\ 


\ 


\. 






















\'A 


v 
























* 


% 
























'$ 


pj 


•>• ■•?■.' 


s 




















';> 


'.^' 



















































7 




































\. 


\ 












.^5 












\ 




V 
























\ 


\ 




\a 













100 200 



300 400 500 600 700 800 900 1000 1100 1200 1300 
RESISTANCE IN OHMS 



Fig. 40 — Input impedance of all loops at 3 kHz measured from station set 
with a simulated intraoffice circuit termination at the central office. Return loss 
circles based on 500-type subset impedance. 



CUSTOMER LOOP PLANT 



3385 



-300 



O -500 




200 



700 800 900 1000 

RESISTANCE IN OHMS 



Fig. 41 — Mean input impedance of nonloaded loops measured from station 
set with: Curve A — simulated four-wire trunk 900 ohms -f 2 fiF central office 
termination; Curve B — simulated two-wire trunk 22-gauge H-88 cable central 
office termination; and Curve C — simulated intraoffice calls condition.